Automated PAT tester with up to 25A Protective Earth test | PAT85

Automated PAT tester with up to 25A Protective Earth test | PAT85

R46,185.00 ex vat

Automated PAT  – Overview

Comprehensive safety testing of electrical equipment is possible with the PAT-85. This compact tester is ideal for measuring the parameters of electrical equipment which affect safety: resistance of protective conductors, insulation resistance, continuity of connections, leakage currents, power as well as RCD and PRCD circuit breakers. The meter performs flawlessly where safety is of paramount importance. It is particularly useful in situations where there is a need for a quick check of power tools, three-phase equipment, or white goods. The touch screen and auto-procedures section make testing quick and efficient. The meter communicates with a label printer or a QR scanner, which greatly facilitates the recordkeeping of tools. This data can be read and added to the meter memory using the optional QR code scanner. The tester is housed in a compact and durable case that provides instrument protection during both measurements and transport.

The meter transmits results via USB, LAN, or WiFi. In addition, it is possible to upload the results to a USB stick. Dedicated PAT Analysis software allows for data management and also reports preparation. In addition, it is possible to use the PAT Server solution. This allows for smooth data management, online uploading to the server, working through a web browser, working in task ordering mode, and storing copies of data on the server.

Automated PAT tester – Features

  • Extensive measuring system enables:
    • protective conductor resistance measurement using current: 200 mA, 10 A, and 25 A
    • measurement of insulation resistance using voltage: 100 V, 250 V, 500 V, and 1000 V
    • measurement of substitute, differential, and touch leakage current
    • functional test
    • test of RCD and PRCD switches
  • Intuitive user interface
  • Integration with a label printer and QR code scanner
  • Robust, compact housing
  • Operation time at rechargeable battery power supply: up to 1 hour

Description

Automated PAT tester with up to 25A Protective Earth test | PAT85

Measurement functions

Range
Resolution
Accuracy
Resistance of protective conductor (PE)  I = 200 mA / 10 A / 25A up to 19.99 Ω from 1 mΩ from ±(3% m.v. + 4 digits)
Insulation resistance UISO =100 V / 250 V / 500 V / 1000 V up to 599.9 MΩ from 1 kΩ ±(5% m.v. + 8 digits)
Current (clamp measurement) up to 24.9 A from 1 mA ±(5% m.v. + 5 digits)
Visual test ✓
Continuity check of protective conductor (PE) ✓
Insulation resistance measurement at three points ✓
IEC cable test ✓
Functional test
Apparent power S up to 3.99 kVA from 1 VA ±(5% m.v. + 3 digits)
Active power P up to 3.99 kW from 1 W ±(5% m.v. + 3 digits)
Reactive power Q up to 3.99 kvar from 1 var ±(5% m.v. + 3 digits)
Power Factor (PF) up to 1.00 0.01 ±(10% m.v. + 5 digits)
Current consumption for power measurement up to 15.99 A 0.01 A ±(2% m.v. + 3 digits)
THD for voltage and current up to 99.9% 0.1% ±(5% m.v. + 5 digits)
Cosφ up to 1.0 0.1 ±(5% m.v. + 5 digits)
Leakage current measurement
PE leakage current and differential leakage current up to 19.9 mA 0.01 mA ±(5% m.v. + 2 digits)
Substitute leakage current up to 19.9 mA 0.01 mA ±(5% m.v. + 2 digits)
Touch leakage current up to 4.999 mA 0.001 mA ±(5% m.v. + 3 digits)
RCD and PRCD switch test
Measurement of RCD parameters according to IEC 61557 up to 300 ms 1 ms ±(2% m.v. + 2 digits)
Measurement of RCD tripping current IA

for sinusoidal residual current (AC type)

up to 30 mA 0.1 mA ±5% IΔn
Measurement of power network parameters
Voltage up to 265.0 V 0.1 V ±(2% m.v. + 2 digits)
Frequency up to 55.0 Hz 0.1 Hz ±(2% m.v. + 2 digits)

Calibration certificates are issued during the production process. New calibration certificates are available upon request at an additional cost.

Automated PAT tester with up to 25A Protective Earth test | PAT85

Brand

Sonel

Sonel Details.
Sonel Logo Square

Reviews

There are no reviews yet.

Be the first to review “Automated PAT tester with up to 25A Protective Earth test | PAT85”