Three-Phase Transformer Turns Ratio Tester – Overview
The great advantage of the Three-Phase Transformer Tester PWR3A is its simple set-up. You simply type in the vector group with the keys to set up, connect the transformer to the device, and release the measurement. All three phases are measured consecutively. All connecting and short-circuited procedures at the primary and secondary voltage sides are performed automatically before each measurement. It is also possible to measure just one phase. An adjustable set value allows an error or deviation of the measured transformation ratio to be displayed. Automatic control of the tap changer is provided. All phases and taps are measured consecutively, and the results are stored inside the instrument and transferred to a PC. The transformer-specific data can be easily programmed via a connected PC but it is also possible via the internal keyboard. The PWR3A is connected to the H.V. and L.V. sides via four connections each. It also powers the test object at a selected voltage, supplied by an internal isolating transformer. An external excitation using different voltages and frequencies is also possible.
Three-Phase Transformer Turns Ratio Tester – Features
• Ratio range from 0.75 to 20,000 (higher ratios with CVT-Ext.)
• Fully automated measurement
• Features market unique Vector Group Detection
• Measuring voltage from 8 V to 230 V
• Measuring voltage up to 5 kV by CVT-Extension: PWR3A-CVT
• Using 3-phase voltage for phase angles other than 0°/180°
• Easy to handle tap changer automatic
• Internal memory stores all dates (Reading with PWR3A-XFER)
• LC display (256 x 128 pixel) with backlight
• Easy input of vector group and measuring conditions
• USB/RS232C port to get full instrument control
• Centronics printer port or built in printer (optional)
• Robust mobile case for field use
• Factory Certificate






Reviews