Handheld Turns Ratio Tester | TRT-H

Handheld Turns Ratio Tester | TRT-H

Handheld Turns Ratio Tester  – Overview

The TRT-H is a battery operated, handheld, fully automatic test set designed for turns ratio, excitation current and phase shift measurements of transformers. The transformer turns ratio is determined by applying AC voltage across high-voltage winding, accurately measuring AC voltage across the corresponding unloaded transformer winding, and then displaying the ratio of these voltages. The user can enter a transformer’s nameplate voltages, so that the turns ratio deviation can be calculated. This feature eliminates any error otherwise caused by an operator’s manual calculation. It compares measured turns ratio with the nameplate ratio and prints out the % of error for each test. Applications include: Turns ratio measurement of distribution transformers; Turns ratio verification of instrument transformers; Turns ratio deviation calculation; Excitation current measurement of distribution and instrument transformers; Phase angle measurement of distribution and instrument transformers; and Polarity check of instrument transformers.

Handheld Turns Ratio Tester – Features

  • Unique handheld instrument
  • Extremely lightweight – only 1.4 kg / 3.1 lbs
  • Measures 3 transformer parameters:
    • Turns ratio
    • Excitation current
    • Phase angle
  • Single-phase test voltage up to 40 V AC
  • Turns ratio accuracy up to ±0.1%
  • Battery-powered
  • Tests single-phase and three-phase transformers

 

Description

Handheld Turns Ratio Tester | TRT-H

Battery
Type: Li-Ion, 14.8 V, 2.9 Ah
Rechargeable
User replaceable
Power Supply Adapter
Input voltage: 90 – 264 V AC, 50/60 Hz
Output voltage: 12-19 V DC
Output current: 2 A DC
Output voltages
40 V, 10 V, 1 V AC
Turns Ratio Measurement Measurement range:
0.8 – 20 000 @40 & 10 V AC
0.8 – 4 000 @1 V AC
Resolution: 5 digits
Typical accuracy: @40 V AC
0.8 – 999: ±0.1%
1 000 – 3 999: ±0.15%
4 000 – 14 999: ±0.25%
15 000 – 20 000: ±0.3%
@10 V AC
0.8 – 999: ±0.2%
1 000 – 3 999: ±0.2%
4 000 – 14 999: ±0.25%
15 000 – 20 000: ±0.3%
@1 V AC
0.8 – 999: ±0.2%
1 000 – 4 000: ±0.2%
Excitation Current Measurement
Measurement range: 0 – 1 A
Resolution: 0.1 mA
Typical accuracy: ±(1% rdg + 0.5 mA)
Environmental protection (IP rating) Device: IP40
Device in plastic case: IP67 (closed lid)
Phase Angle Measurement
Measurement range: 0 – 360º
Resolution: 0.01º
Typical accuracy: ±0.06º
Display
LCD 4.8” display, 240 x 128 pixels
Interface Bluetooth
Internal Memory
100 transformer records
Each record contains up to 15 results
Warranty
3 years + additional 1 year upon registration
on DV Power official website
Environmental Conditions
Operating temperature: -20 ºC – +55 ºC
Storage & transportation: -40 ºC – +70ºC
Humidity: 0% – 95%
relative humidity, noncondensing
Dimensions and Weight
Dimensions (W x H x D): 170 x 310 x 58 mm
Weight: 1.4 kg / 3.1 lbs
Applicable Standards
Installation/Overvoltage category: II
Pollution degree: 2
Safety: LVD 2014/35/EU (CE Conform)
Standard EN 61010-1:2010
EMC: Directive 2014/30/EU (CE Conform)
Standard EN 61326-1:2013

All specifications herein are valid at ambient temperature of +25 °C / +77 °F and standard accessories.

Specifications are subject to change without notice.

Handheld Turns Ratio Tester | TRT-H

Brand

DV Power

IBEKO Power AB, with headquarters in Stockholm (Sweden) and best known through the brand ”DV Power”, has developed radically light and ingenious test solutions for transformers, circuit breakers, and batteries. Founded by a group of engineers with deep knowledge and experience in the power electronics technology area. Sold worldwide – in over 100 countries. Their success is solely based on extensive research, development, and fast commercial application.

Reviews

There are no reviews yet.

Be the first to review “Handheld Turns Ratio Tester | TRT-H”