Three-Phase Transformer Turns Ratio Tester | TRT Std Series

Three-Phase Transformer Turns Ratio Tester | TRT Std Series

Three-Phase Transformer Turns Ratio Tester – Overview

  • True Three-Phase Test Voltage TRT (except TRT03)
  • Highest accuracy for turns ratio, excitation current, and phase angle
  • High measurement resolution
  • Interchangeable cables with TWA
  • Automatic Vector Group Detection
  • Built-in Tap Changer Control Unit
  • DV-TR software is included
  • Magnetic Balance Test
  • Memory store 200 test records. Each consists of 50 test readings
  • USB Flash Drive
  • Optional Built-in Printer

 

Description

Three-Phase Transformer Turns Ratio Tester | TRT Std Series

Mains Power Supply Connection: according to IEC/EN60320-1; UL498, CSA 22.2
Mains supply: 90 – 264 V AC, 50/60 Hz
Input power:
200 VA (for TRT03 and TRT33)
250 VA (for TRT63)
Turns Ratio Measurement Range: 0.8 – 50 000
Resolution: 5 digits
Typical accuracy: @250 V AC
@100 & 80 V AC
0.8 – 999: ±0.03%
0.8 – 999: ±0.05%
1 000 – 3 999: ±0.05%
1 000 – 3 999: ±0.05%
4 000 – 14 999: ±0.05%
4 000 – 14 999: ±0.1%
15 000 – 19 999: ±0.05%
15 000 – 19 999: ±0.2%
20 000 – 50 000: ±0.1%
20 000 – 50 000: ±0.25%
@40 V AC @10 & 8 V AC
0.8 – 999: ±0.05%
0.8 – 999: ±0.05%
1 000 – 3 999: ±0.1%
1 000 – 3 999: ±0.1%
4 000 – 14 999: ±0.2%
4 000 – 15 000: ±0.2%
15 000 – 20 000: ±0.3%
@1 V AC
0.8 – 999: ±0.05%
1 000 – 4 000: ±0.1%
Excitation Current Measurement Range: 0 – 2 A
Resolution:
0.0000 – 9.9999 mA 0.1 μA
10.000 – 99.999 mA 1 μA
100.00 – 999.99 mA 10 μA 1
.0000 – 2.0000 A 100 μA
Typical accuracy: ±(0.25% rdg + 0.5 mA)
Phase Angle Measurement Range: 0 – 360º
Resolution: 0.01º
Typical accuracy: ±0.05º
Test Voltages TRT63A: 1, 8, 40, 100, 250 V AC
TRT63B: 1, 10, 40, 100, 250 V AC
TRT63C: 1, 8, 40, 80, 250 V AC
TRT33A: 1, 8, 40, 100 V AC
TRT33B: 1, 10, 40, 100 V AC
TRT33C: 1, 8, 40, 80 V AC
TRT03A: 8, 40, 100 V AC
TRT03B: 10, 40, 100 V AC
TRT03C: 8, 40, 80 V AC
Display LCD screen 20 characters by 4 lines;
LCD display with backlight, visible in bright sunlight
Interface USB (standard)
RS232 (optional)
Data Storage TRT can store up to 10 000 test results
Dimensions and Weight
Dimensions (W x H x D): 478 x 194 x 390 mm / 18.82 x 7.64 x 15.35 in
Weight: 8 kg / 17.6 lbs (TRT03 and TRT33) 9 kg / 19.8 lbs (TRT63)
Environmental Conditions Operating temperature: -20 ºC – +60 ºC / -4 ºF – +140 ºF
Storage & transportation temperature:
-40 ºC – +70ºC / -40 ºF – +158 ºF
Humidity: 0 – 95% relative humidity, noncondensing
Printer (optional) Built-in thermal printer
Paper width 58 mm / 2.3 in
Printer operating temperature: -20 ºC – +70 ºC / -40 ºF – +158 ºF
Warranty
3 years + 1 additional year upon registration on DV Power official website
Applicable Standards Installation/Overvoltage category: II
Pollution degree: 2
Safety: LVD 2014/35/EU (CE Conform) Standard EN 61010-1:2001
EMC: Directive 2014/30/EU (CE Conform) Standard EN 61326-1:2006
IEEE C57.12.90

All specifications herein are valid at ambient temperature of +25 °C and standard accessories. Specifications are subject to change without notice.

Three-Phase Transformer Turns Ratio Tester | TRT Std Series

Brand

DV Power

IBEKO Power AB, with headquarters in Stockholm (Sweden) and best known through the brand ”DV Power”, has developed radically light and ingenious test solutions for transformers, circuit breakers, and batteries. Founded by a group of engineers with deep knowledge and experience in the power electronics technology area. Sold worldwide – in over 100 countries. Their success is solely based on extensive research, development, and fast commercial application.

Reviews

There are no reviews yet.

Be the first to review “Three-Phase Transformer Turns Ratio Tester | TRT Std Series”