Compact Oxygen Transmitter | Ntron SenzTx

Compact Oxygen Transmitter | Ntron SenzTx

Compact Oxygen Transmitter – Overview

This compact and robust O2 transmitter utilises zirconia or electrochemical technology to give a reliable measurement of oxygen concentration. The zirconia sensor offers fast response time and a long service life with virtually no drift. The electrochemical sensor allows measurement in background gases containing hydrocarbons. The minimum output range of 0 to 1000ppm is ideal for nitrogen generation or glove box monitoring. The SenzTx transmitter can also be supplied with measuring ranges up to 0 to 96% O2 for oxygen concentrators. The flexibility is further enhanced by process connection multiple output options. Applications include Nitrogen Generators, Oxygen Generators, and Glove Boxes.

Compact Oxygen Transmitter  – Features

  • Lightweight and robust (< 0.3Kgs)
  • Zirconia/electrochemical sensor technology options
  • Measurement range: 0 to 1000ppm up to 0 to 100% O2
  • RS485 Modbus Protocol
  • 24VDC power supply
  • KF40 Flange/Flowthrough process connections
  • Orifice process connection options available
  • Combined Sensor & Electronics allows for ease of integration

Description

Compact Oxygen Transmitter | Ntron SenzTx

Technical Specifications
Sensor
Zirconia (ZR) Electrochemical (EC)
Measurement Range* 0…1000 ppmV, 0…1,000 ppmV,
0…1, 0…25, 0…96, 0…100 % 0…1, 0…25 %
Accuracy Please see Accuracy Table
Output Resolution (4…20 mA) 1 ppm V / 0.01 % 0.5 ppmV / 0.01 %
Lower Detection Limit (LDL) 1 ppmV (ppm ranges) / 0.01 % (% ranges)
Sample Flow Rate (application dependent) Flow-through / extractive: 100…500 ml/min (250 ml/min optimal) in a vented atmosphere Direct insertion: Up to 6 m/s
Pressure Range 900…1100 mBarabs
Response Time (T90) < 15 seconds @ +25 °C (+77 °F) within selected range
Operating Temperature Range -25…+60 °C (-13…+140 °F) 0…+45 °C (+32…+113 °F)
Life Expectancy (application dependent) Up to 5 years Up to 18 months
Humidity 0…95 %rh non-condensing (with normal use)
Shelf Life (in original packaging) Unlimited Up to 3 months
Calibration Interval (application dependent) 12 months 3-6 months
*Other measurement ranges are available on request
Transmitter
Electrical
Output Signal 4…20 mA
Digital Communications RS485 Modbus
Electrical Interface Industry standard M12
Power Supply 24 V DC +/- 15 %
Maximum Power Consumption 4.8 W 2.4 W
Cable Length 1 meter (supplied as standard) / 3 meter / 10 meter
Mechanical
Ingress Protection IP66
Housing Material Chromated aluminum
Process Connection Flow-through (1/8” NPT) or KF40 flange
Weight Flow-through: 344 g (12.1 oz) 391 g (13.8 oz)
Flow-through w/orifice: 346 g (12.2 oz) 393 g (13.9 oz)
KF40: 350 g (12.4) oz 397 g (14.0 oz)
Compliance
ETL: UL-61010-1, EMC: EN 50270
Marine approved version available – Lloyd’s Register: EN 60945

 

Accuracy Table
Accuracy at standard temperature and pressure (STP)
Range ZR EC
10 ppm ± 0.5 ppm ±0.5 ppm
100 ppm ± 1 ppm ±1 ppm
1000 ppm ±3 ppm @ 100 ppm
±3 ppm @ 100 ppm
±1 ppm @ 10 ppm
±1 ppm @ 10 ppm
1% ±10 ppm @ 100 ppm
10 ppm @ 100 ppm
25% ± 0.03 % @ 1 % 0.03 % @ 1 %
± 0.02 % @ 0.1 %
±0.02 % @ 0.1 %
96% ± 1 % @ 95 %

Compact Oxygen Transmitter | Ntron SenzTx

Brand

Ntron

Ntron strives to exceed customer expectations by continually innovating better and more efficient gas analysis and control solutions to help maximise process efficiency, improve product quality, protect the health and safety of personnel and the environment, as well as preserve capital equipment and investments.