Description
RCD Tester | MRP-201
RCD trigger test and response time measurement tA
Measurement range according to IEC 61557: 0 ms…the upper limit of the displayed value
| RCD type |
Rated Current
Multiplication
Factor |
Range |
Resolution |
Accuracy |
General
or short delay |
0,5*IΔn |
0…300 ms |
1 ms |
±(2% of reading + 2 digits)* |
| 1*IΔn |
| 2*IΔn |
0…150 ms |
| 5*IΔn |
0…40 ms |
| Selective |
0,5*IΔn |
0…500 ms |
| 1*IΔn |
| 2*IΔn |
0…200 ms |
| 5*IΔn |
0…150 ms |
*for IΔn= 10 mA and 0,5 IΔn accuracy is ±2% of reading + 3 digits
- residual current setting accuracy:
– for 1*IΔn, 2*IΔn and 5*IΔn: 0…8%,
– for 0,5*IΔn : -8…0%
- nominal voltage Un: 220 V, 230 V, 240 V
- work voltage range: 180…270 V
- nominal frequency fn: 50 Hz, 60 Hz
- work frequency range: 45 Hz…65 Hz
RCD disconnecting current measurement for a sine AC test current (IA)
Measurement range according to IEC 61557: (0,3…1,0)IΔn
Selected
rated RCD
current |
Range |
Resolution |
Measurement
current |
Accuracy |
| 10 mA |
3,3…10,0 mA |
0,1 mA |
0,3 mA x IΔn
…1,0 mA x IΔn |
±5% IΔn |
| 30 mA |
9,0…30,0 mA |
| 100 mA |
33…100 mA |
1 mA |
| 300 mA |
90…300 mA |
| 500 mA |
150…500 mA |
- start of measurement from the positive or negative half sine period of the test current
- test current flow time – max. 7510 ms at f=50,0 Hz
RCD disconnecting current measurement for unidirectional pulsed residual current and unidirectional pulsed current with a 6 mA DC offset (IA)
Measurement range according to IEC61557: (0,15…1,4) IΔn for IΔn > 30 mA and (0,15…2)IΔn for IΔn=10 mA
Selected
rated RCD
current |
Range |
Resolution |
Measurement
current |
Accuracy |
| 10 mA |
1,5…20,0 mA |
0,1 mA |
0,15 x IΔn
…2,0 mA x IΔn |
±10% IΔn |
| 30 mA |
4,5…42,0 mA |
| 100 mA |
15…140 mA |
1 mA |
0,15 mA x IΔn
…1,4 mA x IΔn |
±10% IΔn |
| 300 mA |
45…420 mA |
- start of the measurement from the positive or negative half sine period of the test current
- test current flow time – max. 14710 ms at f=50 Hz
RCD response time measurement for the residual DC current (IA)
Measurement range according to IEC61557: (0,2…2)IΔn
Selected
rated RCD
current |
Range |
Resolution |
Measurement
current |
Accuracy |
| 10 mA |
2…20,0 mA |
0,1 mA |
0.2 mA x IΔn
…2,0 mA x IΔn |
±10% IΔn |
| 30 mA |
6…60 mA |
1 mA |
| 100 mA |
20…200 mA |
| 300 mA |
60…600 mA |
- measurement possible for positive or negative residual current
- test current flow time – max. 4500 ms at f=50 Hz
IΔn – rated residual current value RCD
Touch voltage measurement referred to the rated residual current (UB)
Measurement range according to IEC61557: 10,0…99,9 V
| Range |
Resolution |
Measurement current |
Accuracy |
| 0…9,9 V |
0,1 |
0,4 x IΔn |
0…10% IΔn of reading. ± 5 digits |
| 10,0…99,9 V |
0…15% IΔn of reading |
Earthing resistance measurement (RE)
Selected
rated RCD
current |
Range |
Resolution |
Measurement
current |
Accuracy |
| 10 mA |
0,01…5,00 kΩ |
0,01 kΩ |
4 mA |
0…+10% of reading ± 5 digits |
| 30 mA |
0,01…1,66 kΩ |
12 mA |
0…+10% of reading ± 5 digits |
| 100 mA |
1…5000 Ω |
1 Ω |
40 mA |
0…+5% of reading. ± 5 digits |
| 300 mA |
1…166 Ω |
120 mA |
| 500 mA |
1…100 Ω |
200 mA |
Voltage measurement
Measurement range in accordance with IEC 61557: 1,1 Ω…1,99 kΩ
| Range |
Resolution |
Accuracy |
| 0,00…299,9 V |
0,1 V |
±(2% of reading + 6 digits) |
| 300…500 V |
1 V |
±(2% of reading+ 2 digits) |
- frequency range: 45…65 Hz
| Range |
Resolution |
Accuracy |
| 45,0…65,0 Hz |
0,1 Hz |
±(0,1% of reading + 1 digit) |
Electric security:
- type of insulation: double, according to EN 61010 – 1 and IEC 61557
- measurement category: CAT IV 300 V (III 600 V) acc. to EN 61010 – 1
- protection class: IP67
Other technical data:
- power supply: alkaline batteries LR6 (AA) (4 pcs.)
Rated operational conditions:
- operating temperature: -10…+50°C
- storing temperature: -20…70°C
- humidity: 20…80%
Calibration certificates are issued during the production process. New calibration certificates are available upon request at an additional cost.