Insulation Resistance Meter – Overview

Measure insulation resistance up to 2 TΩ. The MIC-2511 may be used to measure the insulation resistance using test voltage up to 2500 V. This surprising tool includes numerous functions. Its parameters, robust casing (IP65 protection level), low battery power consumption, and the ability to recharge during measurements make it a reliable tool that can be used in many areas. The device has built-in help screens with measurement diagrams so you can easily and quickly check and make sure how to connect to a given system depending on the type of measurement performed. It is ideal for checking industrial installations and catenary networks and is also successfully used in residential buildings. It also enables the testing of surge protection devices (SPD). The advantages of this meter are especially appreciated by electricians working in maintenance, testing motors, cables and street lighting. It is also useful for measurements during the construction and maintenance of photovoltaic installations. It is a reliable solution created for the needs of telecommunications network installers and heating network operators, facilitating the control of the alarm system of pre-insulated pipes. Also available as an EPA kit.

Insulation Resistance Meter – Features

  • Measurement voltage within the range of 10…2500 V: selected from 10 V, 25 V, 100 V, 250 V, 500 V, 1000 V, 2500 V, or 10…2500 V selected in steps of 10 V
  • Insulation resistance measurements with a voltage of 10 V of the supervisory loop of fire alarm systems
  • Charts plotted on display during measurements
  • Measurements in electrostatic protected areas (EPA)
  • Correction of insulation resistance result to reference temperature
  • Continuous reading of measured insulation resistance or leakage current
  • Automatic discharge of the measured object’s capacitance upon completion of insulation resistance measurement
  • Sound signaling of five-second time intervals, facilitating capture of time characteristics
  • Timing of measurement times T1, T2 and T3 for measurement of one or two absorption coefficients (Ab1, Ab2 or DAR, PI) within the range of 1… 600 s
  • Automatic measurement of all resistance combinations of 3-, 4- and 5-core cords and power cords using the optional AutoISO-2511 adapter
  • Reading of actual measurement voltage during measurement
  • Measurement current <2 mA
  • Protection against measurement of live objects
  • Two- or three-lead method of insulation resistance measurement

Additional features

  • Measurement of leakage current during measurement of RISO
  • Capacitance measurement during measurement of RISO
  • Low-voltage measurement of circuit continuity and resistance
  • Temperature measurement (with the use of the optional ST-1 temperature probe)
  • Measurement of direct and alternating voltages within the range of 0…1500 V
  • 9999-entry memory, data transmission to PC via USB cable
  • Power supplied by rechargeable battery
  • Backlit keyboard
  • The instrument meets the requirements laid down by standard EN IEC 61557

 

Description

Insulation Resistance Meter | MIC-2511

Measurement range acc. to EN IEC 61557-2 forISOmin=UISOnom/IISOnom…≤ 2 TΩ (IISO=1.6 mA)

Range Resolution Accuracy
0.0…999.9 kΩ 0.1 kΩ ±(3% m.v. + 20 digits)
1.000…9.999 MΩ 0.001 MΩ ±(3% m.v. + 20 digits)
10.00…99.99 MΩ 0.01 MΩ ±(3% m.v. + 20 digits)
100.0…999.9 MΩ 0.1 MΩ ±(3% m.v. + 20 digits)
1.000…9.999 GΩ 0.001 GΩ ±(3% m.v. + 20 digits)
10.00…99.99 GΩ 0.01 GΩ ±(3% m.v. + 20 digits)
100.0…999.9 GΩ 0.1 GΩ ±(3% m.v. + 20 digits)
1.000…2.000 TΩ 0.001 TΩ ±(3% m.v. + 20 digits)

„m.v.” – measured value

 

Values of measured resistance depending on measurement voltage
Voltage Un Measurement range
10 V 10 GΩ
25 V 20 GΩ
50 V 50 GΩ
100 V 100 GΩ
250 V 250 GΩ
500 V 500 GΩ
1000 V 1.00 TΩ
2500 V 2.00 TΩ
DC and AC voltage measurement
Range Resolution Accuracy
0…1500 V 1 V ±(3% m.v. + 2 digits)

frequency range: 45…65 Hz

 

Capacitance measurement

Range Resolution Accuracy
0…999 nF 1 nF ±(5% m.v. + 5 digits)
1.00…9.99 μF 0.01 μF ±(5% m.v. + 5 digits)
Continuity test with current 200 mA

Measurement range acc. to EN IEC 61557-2: 0.10…999 Ω

Range Resolution Accuracy
0.00…19.99 Ω 0.01 Ω ±(2% m.v. + 3 digits)
20.0…199.9 Ω 0.1 Ω ±(2% m.v. + 3 digits)
200…999 Ω 1 Ω ±(4% m.v. + 3 digits)
Temperature measurement
Range Resolution Accuracy
-40.0…99.9°C 0.1°C ±(3% m.v. + 8 digits)
-40.0…211.8°F 0.1°F ±(3% m.v. + 16 digits)
Insulation resistance measurement in EPA areas
Range Resolution Accuracy
for Un = 10 V
0.0…999.9 kΩ 0.1 kΩ ±(8% m.v. + 20 digits)
1.0…9.999 MΩ 0.001 MΩ ±(8% m.v. + 20 digits)
10.00…99.99 MΩ 0.01 MΩ ±(8% m.v. + 20 digits)
100.0…999.9 MΩ 0.1 MΩ ±(8% m.v. + 20 digits)
1.0…10.0 GΩ 0.1 GΩ ±(8% m.v. + 20 digits)
for Un = 100 V
0.0…999.9 kΩ 0.1 kΩ ±(3% m.v. + 20 digits)
1.000…9.999 MΩ 0.001 MΩ ±(3% m.v. + 20 digits)
10.00…99.99 MΩ 0.01 MΩ ±(3% m.v. + 20 digits)
100.0…999.9 MΩ 0.1 MΩ ±(3% m.v. + 20 digits)
1.000…9.999 GΩ 0.001 GΩ ±(3% m.v. + 20 digits)
10.00…99.99 GΩ 0.01 GΩ ±(3% m.v. + 20 digits)
100.0…200.0 GΩ 0.1 GΩ ±(8% m.v. + 20 digits)
for Un = 500 V
0.0…999.9 kΩ 0.1 kΩ ±(3% m.v. + 20 digits)
1.000…9.999 MΩ 0.001 MΩ ±(3% m.v. + 20 digits)
10.00…99.99 MΩ 0.01 MΩ ±(3% m.v. + 20 digits)
100.0…999.9 MΩ 0.1 MΩ ±(3% m.v. + 20 digits)
1.000…9.999 GΩ 0.001 GΩ ±(3% m.v. + 20 digits)
10.00…9999 GΩ 0.01 GΩ ±(3% m.v. + 20 digits)
100.0…999.9 GΩ 0.1 GΩ ±(8% m.v. + 20 digits)
1000 GΩ 1 GΩ ±(8% m.v. + 20 digits)

Calibration certificates are issued during the production process. New calibration certificates are available upon request at an additional cost.