Electrical Installation  Meter with Power Analyzer MPI-540 Overview

The MPI-540 meter is designed for checking industrial and home electrical installations. The measurements taken by the device, determine the safety of the installation. In addition, the user has the possibility to register the parameters of electrical networks located at these facilities. This allows for the measurement of the parameters of protection against electric shock using a single universal device while verifying the quality of electricity. The Auto mode allows significant automation of measurements of the meter and makes it possible to test the functioning of residual current circuit breakers, as well as in pre-programmed measuring sequences, which can be extended with their own sequences. Automatic measurement of insulation resistance of 3-, 4- and 5-wire conductors are possible by using an additional AUTO ISO-1000C adapter.

Datasheet

Description

Electrical Installation Meter MPI-540 Specifications

Measurement of short circuit loop impedance ZL-PE, ZL-N, ZL-L

Test current: 23/40 A; measuring range acc. to IEC 615570,13 – 1999,9 Ω (for 1.2 m test lead):

Display range Resolution Accuracy
0,000 – 19,999 Ω 0,001 Ω ±(5% m.v. + 30 digits)
20,00 – 199,99 Ω 0,01 Ω ±(5% m.v. + 30 digits)
200,0 – 1999,9 Ω 0,1 Ω ±(5% m.v. + 30 digits)
  • Rated voltage: 95 – 270 V (for ZL-PE and ZL-N) and 95 – 440 V (for ZL-L)
  • Frequency: 45 – 65 Hz

Measurement of short circuit loop impedance ZL-PE in RCD mode

Test current: 15 mA, measuring range acc. to IEC 61557: 0,50 – 1999 Ω

Display range Resolution Accuracy
0,00 – 19,99 Ω 0,01 Ω ±(6% m.v. + 10 digits)
20,0 – 199,9 Ω 0,1 Ω ±(6% m.v. + 5 digits)
200 – 1999 Ω 1 Ω ±(6% m.v. + 5 digits)
  • Rated voltage: 95 – 270 V
  • Frequency: 45 – 65 Hz

Measurement of earth resistance RE with the 3p and 4p method

Measuring range acc. to IEC 61557-5: 0,50 Ω -1,99 kΩ for test voltage 50 V, 50 Ω – 1,99 kΩ for test voltage 25 V

Display range Resolution Accuracy
0,00 – 9,99 Ω 0,01 Ω ±(2% m.v. + 4 digits)
10,0 – 99,9 Ω 0,1 Ω ±(2% m.v. + 3 digits)
100 – 999 Ω 1 Ω ±(2% m.v. + 3 digits)
1,00 – 1,99 kΩ 0,01 kΩ ±(2% m.v. + 3 digits)
  • Test voltage: 25 V or 50 V rms
  • Test current: 20 mA, sinusoidal rms 125 Hz (for fn= 50 Hz) and 150 Hz (for fn= 60 Hz)
  • Measurement blocked at interference voltage UN> 24 V
  • Maximum measured interference voltage Unmax= 100 V
  • Maximum resistance of auxiliary earth electrodes 50 kΩ

Selective earth resistance measurement with clamp (3p + clamp)

Measuring range acc. to IEC 61557-5: 1 – 1,99 kΩ

Display range Resolution Accuracy
0,00 – 9,99 Ω 0,01 Ω ±(2% m.v. + 4 digits)
10,0 – 99,9 Ω 0,1 Ω ±(2% m.v. + 4 digits)
100 – 999 Ω 1 Ω ±(2% m.v. + 4 digits)
1,00 – 1,99 kΩ 0,01 kΩ ±(2% m.v. + 4 digits)
  • Measurement with additional current clamp
  • Interference current measuring range: up to 9,99 A

Selective earth measurement with two clamps

Display range Resolution Accuracy
0,00 – 9,99 Ω 0,01 Ω ±(10% m.v. + 4 digits)
10,0 – 19,9 Ω 0,1 Ω ±(10% m.v. + 4 digits)
20,0 – 99,9 Ω 0,1 Ω ±(20% m.v. + 4 digits)
  • Measurement with transmitting and receiving clamps
  • Interference current measuring range: up to 9,99 A

Soil resistivity mesurement (ρ)

Display range Resolution Accuracy
0,00 – 9,99 Ω 0,01 Ω ±(2% m.v. + 4 digits)
10,0 – 99,9 Ω 0,1 Ω ±(2% m.v. + 4 digits)
100 – 999 Ω 1 Ω ±(2% m.v. + 4 digits)
1,00 – 1,99 kΩ 0,01 kΩ ±(2% m.v. + 4 digits)
  • Measurement with Wenner’s method
  • Distance settable in metres or feet
  • Distance range: 1 – 30 m (1 – 90 feet)

Phase sequence indication

  • Phase sequence indication: conforming, non-conforming
  • Mains voltage range U: 100 – 440 V (45 – 65 Hz) L-L
  • Display of phase-to-phase voltage values

Measurements of RCD parameters(voltage range 95 – 270 V):

RCD tripping test and measurement of tripping time tA(for tA measurement function)

RCD type Current Range Resolution Accuracy
General and short-time delay 0,5*IΔn 0 – 300 ms 1 ms ±(2% m.v. + 2 digits)
(for RCD with IΔn = 10 mA and 0,5xIΔn uncertainty: ±(2% m.v. +3 digits)
General and short-time delay 1*IΔn 0 – 300 ms 1 ms ±(2% m.v. + 2 digits)
(for RCD with IΔn = 10 mA and 0,5xIΔn uncertainty: ±(2% m.v. +3 digits)
General and short-time delay 2*IΔn 0 – 150 ms 1 ms ±(2% m.v. + 2 digits)
(for RCD with IΔn = 10 mA and 0,5xIΔn uncertainty: ±(2% m.v. +3 digits)
General and short-time delay 5*IΔn 0 – 40 ms 1 ms ±(2% m.v. + 2 digits)
(for RCD with IΔn = 10 mA and 0,5xIΔn uncertainty: ±(2% m.v. +3 digits)
Selective 0,5*IΔn 0 – 500 ms 1 ms ±(2% m.v. + 2 digits)
(for RCD with IΔn = 10 mA and 0,5xIΔn uncertainty: ±(2% m.v. +3 digits)
Selective 1*IΔn 0 – 200 ms 1 ms ±(2% m.v. + 2 digits)
(for RCD with IΔn = 10 mA and 0,5xIΔn uncertainty: ±(2% m.v. +3 digits)
Selective 2*IΔn 0 – 200 ms 1 ms ±(2% m.v. + 2 digits)
(for RCD with IΔn = 10 mA and 0,5xIΔn uncertainty: ±(2% m.v. +3 digits)
Selective 5*IΔn 0 – 150 ms 1 ms ±(2% m.v. + 2 digits)
(for RCD with IΔn = 10 mA and 0,5xIΔn uncertainty: ±(2% m.v. +3 digits)
  • Accuracy of residual current application: for 0,5*IΔn:-8 – 0% | for 1*IΔn | 2*IΔn | 5*IΔn: 0 – 8%
  • Measurement of RCD tripping current IΔnfor sinusoidal residual current (AC type)

Measurement of RCD tripping current IA for sinusoidal residual current

Rated current Meas. range Resolution Test current Accuracy
10 mA 3,3 – 10,0 mA 0,1 mA 0,3 x IΔn – 1,0 x IΔn ± 5% IΔn
30 mA 9,0 – 30,0 mA 0,1 mA 0,3 x IΔn – 1,0 x IΔn ± 5% IΔn
100 mA 33 – 100 mA 1 mA 0,3 x IΔn – 1,0 x IΔn ± 5% IΔn
300 mA 90 – 300 mA 1 mA 0,3 x IΔn – 1,0 x IΔn ± 5% IΔn
500 mA 150 – 500 mA 1 mA 0,3 x IΔn – 1,0 x IΔn ± 5% IΔn
1000 mA 330 – 1000 mA 1 mA 0,3 x IΔn – 1,0 x IΔn ± 5% IΔn
  • The measurement can be started from a positive or negative half-period of forced leakage current (AC)

Measurement of RCD tripping current IAfor unidirectional residual current and unidirectional with the 6 mA DC bias (type A)

Rated current Meas. range Resolution Test current Accuracy
10 mA 3,5 – 20,0 mA 0,1 mA 0,35 x IΔn – 2,0 x IΔn ± 10% IΔn
30 mA 10,5 – 42,0 mA 0,1 mA 0,35 x IΔn – 1,4 x IΔn ± 10% IΔn
100 mA 35 – 140 mA 1 mA 0,35 x IΔn – 1,4 x IΔn ± 10% IΔn
300 mA 105 – 420 mA 1 mA 0,35 x IΔn – 1,4 x IΔn ± 10% IΔn
500 mA 175 – 700 mA 1 mA 0,35 x IΔn – 1,4 x IΔn ± 10% IΔn
  • Measurement for positive or negative half-periods of forced leakage current

Measurement of RCD tripping current I for direct residual current (type B)

Rated current Meas. range Resolution Test current Accuracy
10 mA 2,0 – 20,0 mA 0,1 mA 0,2 x IΔn – 2,0 x IΔn ± 10% IΔn
30 mA 6 – 60 mA 1 mA 0,2 x IΔn – 2,0 x IΔn ± 10% IΔn
100 mA 20 – 200 mA 1 mA 0,2 x IΔn – 2,0 x IΔn ± 10% IΔn
300 mA 60 – 600 mA 1 mA 0,2 x IΔn – 2,0 x IΔn ± 10% IΔn
500 mA 100 – 1000 mA 1 mA 0,2 x IΔn – 2,0 x IΔn ± 10% IΔn
  • Measurement for positive or negative half-periods of forced leakage current
  • IΔn– rated residual current

Insulation resistance measurements

Measuring range acc. to IEC 61557-2:

  • For Un= 50 V: 50 kΩ- 250 MΩ
  • Un= 100 V: 100 kΩ – 500 MΩ
  • Un= 250 V: 250 kΩ – 999 MΩ
  • For Un= 500 V: 500 kΩ – 2 GΩ
  • For Un= 1000 V: 1 MΩ – 4,99 GΩ
Display range * Resolution Accuracy
0,00 – 1999 kΩ 1 kΩ ±(3% m.v. + 8 digits)
2,00 – 19,99 MΩ 0,01 MΩ ±(3% m.v. + 8 digits)
20,0 – 199,9 MΩ 0,01 MΩ ±(3% m.v. + 8 digits)
200 – 999 MΩ 1 MΩ ±(3% m.v. + 8 digits)
1,00 – 4,99 GΩ 0,01 GΩ ±(4% m.v. + 6 digits)
5 – 9,99 Ω 0,01 GΩ unspecified

*not greater than measuring range for given voltage

Low-voltage measurement of resistance and circuit continuity

Measurement of protective conductor continuity with the ±200 mA current, IEC 61557-4: 0,12 – 400 Ω

Display range Resolution Accuracy
0,00 – 19,99 Ω 0,01 Ω ±(2% m.v. + 3 digits)
20,0 – 199,9 Ω 0,1 Ω ±(2% m.v. + 3 digits)
200 – 400 Ω 1 Ω ±(2% m.v. + 3 digits)
  • Voltage on open terminals: 4 – 9 V
  • Output current at R < 2 Ω: min. 200 mA
  • Autocalibration of test leads
  • Measurements for both current polarities

Illuminance measurement

Display range Resolution Accuracy
0,1 – 99,9 lx 0,1 lx ±(5% m.v. + 2 digits)
100 – 999 lx 1 lx ±(5% m.v. + 2 digits)
1,00 – 9,99 klx 0,01 klx ±(5% m.v. + 2 digits)
10,0 – 19,9 klx 0,1 klx ±(5% m.v. + 2 digits)

Measurement in luxes (lx) or feet-candles (fc)

Three-phase recorder of electrical network parameters

The device is designed to work with networks:

  • With nominal frequency 50/60 Hz
  • With nominal voltage: 64/110 V | 110/190 V | 115/200 V | 127/220 V | 220/380 V | 230/400 V | 240/415 V | 254/440 V | 290/500 V
  • DC network

Supported networks:

  • Single-phase
  • Two-phase with common N conductor
  • Three-phase star connection N with and without a conductor
  • Three-phase delta

Parameters of analyzer:

Parameter Measurement range Max. resolution Accuracy
Alternating voltage (TRMS) 0,0 – 500 V 0,01 % Unom ±0,5% Unom
Alternating current TRMS depending on clamp* 0,01% Inom ±2% m.v. for m.v. ≥ 10% Inom±2% Inom for m.v.
Frequency 40,00 – 70,00 Hz 0,01 Hz ±0,05 Hz
Active, reactive, apparent and distortion power depending of configuration (trasformers, clamp) up to for decimal places depending of configuration (trasformers, clamp)
Active, reactive apparent energy depending of configuration (trasformers, clamp) up to for decimal places as power error
cosφ  and power factor (PF 0,00 – 1,00 0,01 ±0,03
Harmonics Voltage as for alternating voltage as for alternating voltage ±5% m.v. for m.v. ≥ 3% Unom±0,15% Unom for m.v.
Harmonics Current as for alternating voltage as for alternating voltage ±5% m.v. for m.v. ≥ 10% Inom±0,5% Inom for m.v.
THD Voltage 0.0 – 100.0% (in regards to the rms value) 0,1% ±5%
THD Current 0.0 – 100.0% (in regards to the rms value) 0,1% ±5%
Voltage asymmetry Voltage and current 0,0 – 10,0% 0,1% ±0,15% (absolute error)