Three Phase Transformer Measuring Bridge | MLS 7100

Three Phase Transformer Measuring Bridge | MLS 7100

Three-Phase Transformer Measuring Bridge – Overview

The MLS 7100 was particularly designed to simplify the determination of transformer core and copper losses, which is an ideal choice when working on site. The measuring bridge features open-circuit as well as short-circuit measuring. Many transformers can be directly connected to the MLS 7100 without needing further transducers. Core losses are an important transformer quantity in electrical efficiency, operating expenses, and the overall transformer value.

Steel losses are typically determined using open-circuit measurement, as a relatively small magnetising current is flowing. Using this technique, the copper losses are minimized due to the square correlation of power and current. Copper losses are determined using short circuit measurement, as the magnetising modulation of the steel core should be minimized. In addition, the short circuit voltage is determined this way, which is also an important quantity.

Three Phase Transformer Measuring Bridge – Features

  • Open circuit measurements
  • Short circuit measurements
  • Free selectable voltage and current dividers
  • 1000 kV with transducer
  • 1000 kA with transducer
  • 550 V (chained) 6 A directly connectable
  • Measures and displays:
    • Voltages
    • Currents
    • Power
    • Short Circuit Values
    • Frequency
  • Centronics printer port
  • RS232C port for external control

Datasheet

Description

Three-Phase Transformer Measuring Bridge MLS700

Technical Specifications

Transformer loss measuring

Transformer loses: 100 – 2500 VA
Frequency: 40 – 70 Hz
Test voltages: 1000 kV AC max. with transducer
100 – 500 V AC directly connectable
No-Load Currents: 1000 kA max. with transducer
1 – 5 A directly connectable
Short circuit measuring
Short circuit losses: 100 – 2500 VA
Frequency: 40 – 70 Hz
Short circuit voltage: 1000 kV AC max. with transducer
100 – 500 V AC directly connectable
Measuring current: 1000 kA max. with transducer
1 – 5 A directly connectable
Display of Results: Version 2.0
Star Connection: Chained or unchained with connected Neutral
Delta Connection: Chained or unchained with virtual Neutral

Measuring inputs

Secondary transducer current: 5 A
Secondary transducer voltage: 500 V (chained)
Measuring errors: NV / MV = Nominal / Measuring Value
Current: +/-(0,25 % of NV + 1 Digit)For MV > 5 % of NV
Voltage: +/-(0,25 % of NV + 1 Digit)
Power: +/-(0,5 % of NV + 1 Digit)
Powerfactor: +/- 0.02 with Current / Voltage > 15 % of NV
Frequency: 0.02 Hz
Display: LC-Display 110 x 60 mm with backlight
Character height: 3mm and 6mm
LC contrast: selectable by keys

Transducer options

Primary transducer current: 5 – 1.000.000 A (default: 5 A)
Primary transducer voltage: 500 – 1.000.000 V (default: 500 V)

Transformer preferences

Vector group: Y, D N y,d,z n 0..11
Nominal transformer power: 1 – 1000 MVA
Nominal transfer. voltage (HV, LV): 500 V – 1.000.000 V
Nominal transformer current: 1 – 1.000.000 A
Short circuit voltage: 1 – 30 % of nominal voltage
Frequency: 40 – 70 Hz

Connectors

Ports: RS232C, Centronics printer port
Warning light: shows device activity
Limit lamp: shows set point voltage status
Dimensions: 19″ rack, 4 HE
Weight: approx. 9 kg

Three Phase Transformer Measuring Bridge  MLS 7100