Multi-function Electrical Installation Meter – Overview

This Multifunctional Electrical Installations Meter performs complete tests and verifies electrical installations according to the most common safety standards (IEC 61557, VDE 0100, BS7671). The test includes various short circuit loop impedance tests, multiple RCD breaker tests, low voltage resistance measurements of protective circuits, voltage measurements, and frequency measurements.

Multi-function Electrical Installation Meter – Features

Measurement of short circuit loop parameters

  • Measurement of short circuit loop impedance in networks with rated voltage: 220/380 V, 230 V/400 V, 240/415 V and frequency 45 – 65 Hz, operating voltage range: 180 – 460 V
  • Indication of short circuit loop resistance R and short circuit loop reactance X
  • Measurements of short circuit loop impedance with 15 mA current, without tripping the RCD circuit breaker
  • Maximum test current: 7.6 A (at 230 V), 13.3 A (at 400 V)

Testing RCD breakers of AC, A types

  • Testing of prompt, short-delay and selective RCDs with rated current values 10 | 15 | 30 | 100 | 300 | 500 mA
  • Measurement of IA trip current and tripping time tA for currents 0.5 IΔn, 1 IΔn, 2 IΔn, 5 IΔn • RE and UB measurement without RCD tripping
  • The extended AUTO function of RCD measurement, with the possibility of measuring ZL-PE with low current
  • Measurement of IA and tA during one RCD tripping

Insulation resistance measurement

  • Test voltage 100 V, 250 V, 500 V

Measurement of resistance of protective conductors and equipotential bondings

  • Measurement of protective connections continuity with a ±200 mA current in accordance with EN 61557-4
  • Autocalibration of test leads – any leads can be used
  • Low current resistance measurement with sound signalling

Phase sequence indication

Additional functions

  • Checking the correctness of PE connection using a contact electrode
  • Measurement of voltage (0 – 500 V) and network frequency
  • The memory of 990 results, wireless data transmission to a computer
  • Backlit keypad

Datasheet

Description

Multi-function Electrical Installation Meter MPI-506 Specifications

Measurement of short circuit loop impedance ZL-PE, ZL-N, ZL-L

Test current: 7.6/13.3 A; test range according to EN 61557-3 : 0,13 – 1999 Ω :

Display range Resolution Accuracy
0,000 – 19,99 Ω 0,01 Ω ±(5% m.v. + 3 digits)
20,00 – 199,9 Ω 0,1 Ω ±(5% m.v. + 3 digits)
200,0 – 1999 Ω 1 Ω ±(5% m.v. + 3 digits)

Measurement of short circuit loop impedance ZL-PE in RCD mode

Test current: 15 mA, test range acc. to EN 61557-3: 0,50 – 1999 Ω

Display range Resolution Accuracy
0,00 – 19,99 Ω 0,01 Ω ±(6% m.v. + 10 digits)
20,0 – 199,9 Ω 0,1 Ω ±(6% m.v. + 5 digits)
200 – 1999 Ω 1 Ω ±(6% m.v. + 5 digits)

Insulation resistance measurement

Test range acc. to IEC 61557-2

  • UISO :
    • 100 V : 100 kΩ – 99.9 MΩ
    • 250 V : 250 kΩ – 199.9 MΩ
    • 500 V : 500 kΩ – 599.9 MΩ
Display rangefor UISO= 100 V Resolution Accuracy
0 – 1999 kΩ 1 kΩ ±(5% m.v. + 8 digits)
2,00 – 19,99 MΩ 0,01 MΩ ±(5% m.v. + 8 digits)
20,0 – 99,9 MΩ 0,1 MΩ ±(5% m.v. + 8 digits)

 

Display rangefor UISO= 250 V Resolution Accuracy
0 – 1999 kΩ 1 kΩ ±(5% m.v. + 8 digits)
2,00 – 19,99 MΩ 0,01 MΩ ±(5% m.v. + 8 digits)
20,0 – 99,9 MΩ 0,1 MΩ ±(5% m.v. + 8 digits)

 

Display rangefor UISO= 500 V Resolution Accuracy
0 – 1999 kΩ 1 kΩ ±(5% m.v. + 8 digits)
2,00 – 19,99 MΩ 0,01 MΩ ±(5% m.v. + 8 digits)
20,0 – 99,9 MΩ 0,1 MΩ ±(5% m.v. + 8 digits)

Phase sequence indication

  • Phase sequence indication: compliant, non-compliant
  • Network voltage range U: 100 – 440 V
  • Display the values phase-to-phase voltage values

Measurements of RCD parameters(voltage range 180 – 270 V):

RCD tripping test and measurement of tripping time tA(for tA measurement function)

RCD type Current Range Resolution Accuracy
General 0,5*IΔn 0 – 300 ms 1 ms ±(2% m.v. + 2 digits)
General 1*IΔn 0 – 300 ms 1 ms ±(2% m.v. + 2 digits)
General 2*IΔn 0 – 150 ms 1 ms ±(2% m.v. + 2 digits)
General 5*IΔn 0 – 40 ms 1 ms ±(2% m.v. + 2 digits)
Selective 0,5*IΔn 0 – 500 ms 1 ms ±(2% m.v. + 2 digits)
Selective 1*IΔn 0 – 500 ms 1 ms ±(2% m.v. + 2 digits)
Selective 2*IΔn 0 – 200 ms 1 ms ±(2% m.v. + 2 digits)
Selective 5*IΔn 0 – 150 ms 1 ms ±(2% m.v. + 2 digits)

Measurement of RCD tripping current IA for sinusoidal residual current

Rated current Meas. range Resolution Test current Accuracy
10 mA 3,0 – 10,0 mA 0,1 mA 0,3 x IΔn – 1,0 x IΔn ± 5% IΔn
15 mA 4.5 – 15,0 mA 0,1 mA 0,3 x IΔn – 1,0 x IΔn ± 5% I?n
30 mA 9.0- 30,0 mA 0.1 mA 0,3 x IΔn – 1,0 x IΔn ± 5% IΔn
100 mA 30 – 100 mA 1 mA 0,3 x IΔn – 1,0 x IΔn ± 5% IΔn
300 mA 90 – 300 mA 1 mA 0,3 x IΔn – 1,0 x IΔn ± 5% IΔn
500 mA 150 – 500 mA 1 mA 0,3 x IΔn – 1,0 x IΔn ± 5% IΔn
  • Measurement starts with a positive or negative half period of force current

Measurement of RCD tripping current IA for single direction pulsating differential current

Rated current Meas. range Resolution Test current Accuracy
10 mA 3,5 – 20,0 mA 0,1 mA 0,35 x IΔn – 2,0 x IΔn ± 10% IΔn
15 mA 5,3 – 21,0 mA 0,1 mA 0,35 x IΔn – 1,4 x IΔn ± 10% IΔn
30 mA 10,5- 42,0 mA 0,1 mA 0,35 x IΔn – 1,4 x IΔn ± 10% IΔn
100 mA 35,0 – 140 mA 1 mA 0,35 x IΔn – 1,4 x IΔn ± 10% IΔn
300 mA 105- 420 mA 1 mA 0,35 x IΔn – 1,4 x IΔn ± 10% IΔn
  • Measurement for positive or negative half-periods of forced leakage current

Multifunction Meter MPI-506 Technical data

Safety and operating conditions

  • Measuring category acc. to EN 61010: IV 300 V (III 600 V)
  • Ingress protection: IP67
  • Type of insulation acc. to EN 61010-1 and IEC 61557: double
  • Dimensions: 220 x 98 x 58 mm
  • Weight: ca. 0.8 kg

Memory and communication

  • Memory: 990
  • Data transmission: Bluetooth

Other data

  • Number of Z or RCD measurements >5000 (2 measurements/min)
  • The product meets the EMC (emission for the industrial environment) requirements according to standards: EN 61326-1, EN 61326-2-2

Calibration certificates are issued during the production process. New calibration certificates are available upon request at an additional cost.