Indoor Differential Pressure Transmitter | PMM330

Indoor Differential Pressure Transmitter | PMM330

Indoor Differential Pressure Transmitter – Overview

This compact and easy-to-install sensor is a hot-wire type differential pressure sensor designed for small differential pressures and low air velocities. The built-in square root function is used for converting measurement into air velocity, and it provides flexible output options, making it an ideal choice for various differential pressure measurement applications. It has a high sensitivity at low differential pressure with low zero-point drift and a minimum measurable value as low as 1 Pa. It has a pressure resistance of up to 1 bar, and a differential pressure measurement range of ±50 … ±1500 Pa.  There is also a DIP switch to adjust the range and square root function. Suitable for use in environmental monitoring (eg. clean rooms, HVAC) and differential pressure monitoring (eg. air ducts, filters, and airflow monitoring).

Indoor Differential Pressure Transmitter – Features

  • Suitable for HVAC and light industry
  • Measuring element: Hot-wire type diff. pressure sensor, flow-through
  • Measuring range : ±50 … ±1500 Pa
  • Output: 4 … 20 mA / 0 … 10 V / RS-485
  • Accuracy : ±1.5% F.S. ±3% M.V.
  • IP rating: IP65

Description

Indoor Differential Pressure Transmitter | PMM330

Measurement
Measuring element Hot-wire type diff. pressure sensor, flow-through
Measuring range ±50 … ±1500 Pa
Output
Output 4 … 20 mA / 0 … 10 V / RS-485
Signal connection 3-wire
Load resistance Current output: ≦ 500 Ω
Voltage output: ≧10 KΩ
Response time t63 ≦ 2 ms
Display type LCD Module with backlight, double line character
Display range Upon request, 2 decimal places (as unit is Pa: 1 decimal place)
Digit height 5.56 mm
Accuracy (at 25°C)
Accuracy ±1.5% F.S. ±3% M.V.
Temperature influence 1% m.v. per 10°C
Environment
Measuring medium Air
Operating temperature 0 … 50°C
Operating humidity 0 … 95%RH (Non-condensing)
Storage temperature -20 … +60°C
Electrical
Power supply DC 24 V ±10% & AC 24 V ±10%
Current consumption DC 24 V: ≦45 mA (Display) / ≦40 mA(Non-display)
AC 24 V: ≦95 mA (Display) / ≦90 mA(Non-display)
Overvoltage protection ≦DC 40 V
Electrical connection M type ( M12 – 4 PIN connector ) / ( M12 – 5 PIN connector )
N type ( M16 plastic cable gland )
*M type with 2 m cable
Installation
Installation Indoor wall type
Protection
IP rating IP65
Electrical protection ■ Over-voltage
■ Reverse polarity
■ Short circuit
Pressure resistance 1 bar
Burst pressure 3 bar
Certification
Certification CE
Material
Housing PC fire-proof class(PC-110)(UL94V-2)
Weight Display: 152 g
Non-display: 127 g
Note: Design and specifications are subject to change without notice.
Note: If the product has RS-485 function, to avoid damaging product, please make sure the product and the device which connects with RS-485 are on common ground.